Industrial Automation & IoT Solutions Across Saudi Arabia

info@rewellxarabia.com +966 54 170 6399

Energy Intelligence

REECON RE96

Panel-mount, Class 0.2 three-phase smart energy meter & protection relay

Reecon Re96 Panel Mount Energy Meter

REECON RE96 panel-mount three-phase energy meter

At a glance

Typical use cases

REECON is the energy intelligence product line engineered by Epteck GmbH, Germany, and supplied and supported in the Kingdom by Rewellx Arabia. The RE96 mounts in the standard 96 × 96 cutout of an LT panel, sub-distribution board or motor control center, replacing a conventional panel meter with Class 0.2 metering, configurable protection and remote visibility. Multiple meters connect over Wi-Fi, Ethernet or RS485 Modbus, so a whole plant is monitored and alarmed from one login.

Main-incomer metering

Real-time load, power factor and consumption at the LT panel main incomer

Sub-metering

Per department, production line, machine group or tenant for cost allocation

Energy audits & reporting

Time-stamped kWh records, load-trend charts and downloadable reports

Power-quality monitoring

THD (voltage and current), phase angle, voltage sag, phase loss and sequence

Protection & cutoff

Emergency load cutoff via contactor, ACB, VCB or shunt MCB on configured faults

Reactive-power compensation

Relay switching of capacitor banks on real-time power-factor thresholds

Demand response

Grid, solar or generator changeover and load shedding at peak tariff

Predictive maintenance

Device temperature, load anomalies and event history for condition-based maintenance

Typical environments: manufacturing plants, textile mills, food processing, chemical and petrochemical facilities, warehouses, commercial buildings, hospitals and healthcare facilities.

Versions

REECON RE96 (Wi-Fi)
REECON RE96 LoRa
Best for

Sites with Wi-Fi or Ethernet backhaul

Large sites without reliable Wi-Fi

Class 0.2 energy metering, protection suite, FSTN display
Wi-Fi, BLE 5.0, Ethernet and RS485
Relay output and digital input
24 V DC backup input (optional)
LoRa long range add-on (LoRaWAN 1.0.3 / P2P, up to 15 km)
Technical data

Electrical & measurement

Connection type

3P4W (three-phase, four-wire)

Operating voltage

150–270 V AC (L–N), rated 230 V AC, 50/60 Hz

Power / current consumption

2.5–8.5 W (typ. 5.5 W; up to 10 W momentarily); 15–40 mA (typ. 25 mA)

Backup supply

Optional 24 V DC backup input keeps the device running during three-phase outages

Voltage measuring range

0–655 V, resolution 0.01 V

Current measuring range

0.005–6 A via CT secondary (resolution 0.001 A); 5 A-secondary CTs, e.g. 100/5 A

Active / reactive power

−32.768 to +32.767 kW / kVAr, resolution 1 W / VAr

Apparent power

0 to +32.767 kVA, resolution 1 VA

Frequency

45–65 Hz, resolution 0.01 Hz

Power factor / phase angle

−1.000 to +1.000 (0.001) / −180° to +180°

Harmonics

THD+N 0.00–99.99 %; THD and harmonic components 0.00–399 %

Measurement time

1 s typical

Accuracy: active / reactive energy

Class 0.2 / Class 0.5 (0.1 A ≤ Irms ≤ 100 A)

Accuracy: V, I, P, Q, S, PF, f, phase angle

±0.5 %

Accuracy: THD+N, THD, harmonics

5 % relative error

Processing, communication & I/O

Main SoC

Dual-core 32-bit Xtensa LX7, up to 240 MHz, 512 kB SRAM, 8 kB FRAM

Device sensors

Temperature sensor (−10 to +85 °C, ±1 °C); 3-axis accelerometer (±2/4/8/16 g, 1 Hz–5.3 kHz)

Communication

Wi-Fi, BLE 5.0, Ethernet (Modbus TCP), RS485 (Modbus RTU slave); LoRa add-on module

Digital input

1 × 22–24 V DC (typ. 24 V DC), isolated ground

Relay output

1 × NC/NO/COM, 30 V DC / 250 V AC, 3 A for an external contactor, ACB, VCB or shunt MCB (not for direct three-phase load switching)

USB-C

USB 1.1 full-speed OTG, CDC ECM for commissioning and debugging

Display

FSTN monochrome, 79 × 70 mm; 11 live parameter pages plus error, IP and info pages; 4 buttons; password-protected configuration; 85 dB buzzer

Modbus / SCADA integration

46 read-only 16-bit input registers for all live electrical parameters, energy and temperature; function code 0x03; recommended polling 100 ms (RTU) / 1000 ms scan (TCP)

Mechanical & environmental

Dimensions (L × W × H)

104 × 104 × 88 mm (±2 mm)

Panel cutout

Standard 96 × 96 mm, 92.5 × 92.5 mm

Weight

315 g (±10 g)

Operating / storage temperature

−10 to +70 °C / −20 to +80 °C

Humidity

5–85 % RH, non-condensing

Mounting

Panel front of distribution board or LT panel; 4 tool-free clips

Usage / protection

Indoor use; display and buttons on the front, all live terminals behind the panel; passive cooling

Reecon Re96 Key Dimensions

Key dimensions

Protection functions

Over/under voltage

Per-phase limits, affected line shown on the display, automatic re-latch when voltage returns within limits

Over-current

Independent per-phase thresholds with automatic load cutoff and recovery

Over-temperature

Load switched off above the 70 °C internal limit, continuous buzzer until the device cools down

Phase failure & voltage sag

Per-line detection, protective shutdown and automatic resume on restoration

Sequence monitoring

Phase (seq V) and CT/current (seq I) sequence-error detection

Neutral over-current

Configurable threshold for resultant neutral current, with buzzer warning and logging

Metering-chip fault

CHIP OFF error with load cutoff and continuous buzzer

Manual override

Password-protected local override at the panel, logged and shown in the app and dashboard

Ordering information

Product

REECON RE96

Versions

REECON RE96 (Wi-Fi)  |  REECON RE96 LoRa

CT requirement

3 × CTs with 5 A secondary (e.g. 100/5 A), sized to the panel load

Add-on options

LoRa module  |  24 V DC backup power supply

Software

TelliX mobile app (Google Play and Apple App Store) and web dashboard

To size your installation, send us

Your site location and the number of panels or meters, the main incomer and feeder ratings (A), and a photo of the panel with the existing meter cutout.